Title: Heating, Ventilating, and Air-Conditioning (HVAC)
1Chapter 21
- Heating, Ventilating, and Air-Conditioning (HVAC)
2Overview
Code Requirements
Heating Systems
HVAC Drawings
Zone Control
3 Methods of Heat Transfer? Hint (C.C.R)
3Introduction
- Heating, ventilating, and air-conditioning (HVAC)
- Heating and air-conditioning equipment, and
systems found in a building - Also referred to as the mechanical system
- Regulates temperature
- International Residential Code (IRC)
- Requires a heating unit in any residence built in
an area where winter design temperature is below
60
4Thermal Calculations for Heating/Cooling
- Necessary to establish the correct
- Furnace
- Ductwork
- Supply
- Return register specifications
- Historical primary use
- Calculate design heat load of houses to estimate
gas and oil heating systems size
5Thermal Calculations for Heating/Cooling (contd.)
- HVAC terminology
- Btu
- Indoor Air Quality (IAQ)
- Duct loss
- Cubic Feet/ Min. (CFM)
- Heat transfer multiplier
- Indoor temperature
- Air Changes per Hour (ACH)
- Indoor wet bulb
- Infiltration
- Internal heat gain
- Latent load
- Mechanical ventilation
6Thermal Calculations for Heating/Cooling (contd.)
- HVAC terminology (contd.)
- Outdoor temperature
- Outdoor wet bulb
- R-factor
- Sensible load calculations
- Temperature difference
- U-factor
7Thermostats
- Automatic mechanism for controlling heating or
cooling by a central or zonal system - Location is important
8Exhaust Systems Code Requirements
- Exhausts are part of the HVAC system
- Exhaust systems are required to remove odors,
steam, moisture, and pollutants - Refer to the text for basic general code
requirements
9HVAC Code Requirements
- National Energy Conservation Code regulates the
design and construction of - Exterior envelope and selection of HVAC
- Service water heating
- Electrical distribution
- Illuminating systems and required equipment
- Refer to the text for general code requirements
10Code Requirements
- IECC is updated every three years and is designed
to provide an energy efficient environment for
humans - Equipment in a garage must be protected from
automobile impact (slab on grade construction
would have a 18 platform) - Programmable Thermostat
- Exterior (Building) envelope is space that is
heated and cooled - Conditioned (finished square footage)
- Unconditioned (basement unfinished)
- Must be separated by a door
11Code Requirements
- A door or access large enough to remove largest
piece of equipment - Unobstructed working space not less than 30 wide
and high should be provided next to the control
side of the equipment (Furnace, WH) - An GFCI electrical outlet and lighting fixture
should be provided near the equipment and have a
switch at the doorway or access (In attic) - Equipment located on the ground should be
supported on a concrete slab and be at least 3
above the ground. (AC units) - Fuel burning warm-air furnaces must be supplied
with combustion air - All exterior ducting (Avoid at all costs) should
be weatherproof and insulated - In basements all supply lines should be insulated
with R-4.2 insulation unless wall drapes are used
to consider it conditioned space
12Minimum Dimensions
- Furnace 24 x 30
- Water Heater 18-24 Diameter
- Electrical Panel 30 open space
- Pex Piping
13Duct Systems
14Central Forced-Air Systems
15Forced Air Systems
- A fan forces air into ducts that connect to air
supply registers - Air is heated during the heating cycle and the
combustion is vented out flue - Cooled air is passed over a cooling coil which is
cooled with a refrigerant (Puron)
16Forced-Air Heating Plans
- Complete forced-air heating plans show
- Size, location, and number of British thermal
units (Btu) dispersed from warm-air supplies - Location and size of cold-air return
- Location, type, and output of furnace
- Providing duct space (i.e., chase)
- When ducted heating and cooling systems are used,
duct location becomes important
17Central Air Systems
- Rules to Design
- Place Central Air Condenser unit at shortest
straight line to exterior side or rear of home
for coil (efficiency)
- Place Ducting trunks cold air returns and supply
lines to one side of bearing wall (Stairs) - Add Combustion Air Intake direct line same
direction floor joist are running
18Zone Control Systems
- One heater and one thermostat per room
- No duct work
- Only heaters in occupied rooms need to be turned
on - Types
- Baseboard
- Fan heaters
- Split systems
19Alternate Method using Zone Controls
- Individual rooms are heated and cooled as needed
20Hot Water System
- Water is circulated through a radiator after
being heated in an oil- or gas-fired boiler - One-pipe system has heated water pass through
radiators and returns in the same pipe to the
boiler - Radiant Flooring is growing in popularity
21Hot Water Systems
- Water is heated in an oil- or gas-fired boiler
- Then circulated through pipes to radiators or
convectors
22Radiant Heat
- Radiant heating and cooling systems
- Control surface temperatures
- Minimize excessive air motion
- Annual operating cost savings of 20 to 50
- Lower thermostat settings
- Superior, cost-effective design
23Heat Pump/ Geothermal / Passive Solar Systems
- Heat is extracted from outside air and pumped
through a compressor into the structure - Heat pump systems are 30 to 50 percent more
efficient then forced air systems - Air is cleaner and fresher with a heat pump system
24Heat Pump Systems
- Forced-air central heating and cooling system
- Compressor and circulating refrigerant system
25Exhaust System Code Requirements
- Vented hoods must have back draft damper
- Direct vent to exterior suggested for gas or
exhaust fan in kitchen - If gas dryer or other fuel burning appliance (Fan
is good idea) - Clothes dryer vents independent from all other
systems. - No screws in vent
- Back draft damper
- 4 duct no longer than 25
- Total length reduced 2.5 for each 45 bend and 5
for each 90 bend
26Heat Recovery and Ventilation
- Uses a counter flow heat exchanger between
inbound and outbound airflow - Air pollutants
- Principle reason for installation
- Air-to-air heat exchangers
- Pulls polluted, stale, warm air from the space
and transfers heat in that air to fresh, cold air
being pulled into the space
27(No Transcript)
28Gas lines
- Meter
- Pressurized Gas
- 2lb
- 4 oz
29HVAC Drawings
- Drawings for the HVAC system show
- Size and location of all equipment, ductwork, and
components - Use accurate symbols, specifications, notes, and
schedules - Form the basis of contract requirements for
construction
30(No Transcript)
31(No Transcript)
32Residential HVAC Drawings
- Show Thermostat location
- Heat Register Locations
- 4 x 10 floor or 2 x 10 under cabinet
- Cold air return is needed for every 5 heat
registers - 14 x 8 single or 30 x 8 double
- Size of room and use determines number of
registers needed 150 square feet Single
33Residential HVAC Drawings
Show Supply and Return Main Trunk Lines Dryer
Vent Location Combustion Air Location